2753080000 is listed in the Current Sense Transformers range at ChipApex. The manufacturer field lists Weidmüller. Its product description is KCMA-28-300-1A-1.5VA-1. Review the specifications below when checking this part for your BOM.
Current Sense Transformers specifications for 2753080000
- Description:KCMA-28-300-1A-1.5VA-1
- Series:-
- Mfr:Weidmüller
- Package:Box
- Frequency Range:50Hz
- Type:Non-Invasive (Split Core)
- Inductance:-
- ET (Volt-Time):-
- Current Ratio:-
- DC Resistance (DCR):-
- Ratings:-
- Mounting Type:Free Hanging (In-Line)
- Size / Dimension:2.323" L x 1.929" W (59.00mm x 49.00mm)
- Height - Seated (Max):3.154" (80.11mm)
- Termination Style:Wire Leads
- Turns Ratio - Primary:Secondary:-
- Current Rating (Amps):300 A
Current Sense Transformers datasheet and documents for 2753080000
Current Sense Transformers Overview
The Weidmüller 2753080000 is a split-core current transformer designed for precise measurement of load current consumption using RMS value methods. It features a primary current rating of 300 A and a maximum secondary current of 1 A. The device supports a load capacity of 1.5 VA and adheres to tolerance class 1. With an IP20 protection degree, it utilizes wire leads for termination and operates within a minimum temperature range of -5°C.
Current Sense Transformers Feature Summary
- Split-core design enabling installation without disconnecting the primary cable
- Asymmetrical cable feed-through capability for flexible mounting configurations
- RMS value measurement method ensures accurate current consumption monitoring
Current Sense Transformers Applications
- Industrial current sensing applications requiring non-intrusive measurement
- Monitoring current consumption of connected loads in electrical systems
- Integration into control systems utilizing RMS value processing methods
Current Sense Transformers Procurement Notes
Verify that the required primary current does not exceed 300 A and the burden load remains within 1.5 VA limits. Confirm that the operating environment temperature stays above -5°C. Ensure the application accommodates the asymmetrical cable feed-through geometry and wire lead termination style specified for this component.
Current Sense Transformers Selection Notes
Select this model when a split-core configuration is necessary to avoid breaking the primary conductor. The 300 A primary rating suits high-current industrial circuits. The 1 A secondary output requires compatible downstream instrumentation. Verify that the physical space allows for the 49 mm width and asymmetrical opening mechanism during installation.
Current Sense Transformers Part Context
This component belongs to the KCMA series of industrial current transformers manufactured by Weidmüller. It is categorized under current sense transformers intended for precise electrical monitoring. The part number 2753080000 corresponds to the specific variant with 300 A primary current and 1 A secondary output capabilities.
Current Sense Transformers Replacement Considerations
No public confirmed substitute part numbers are available for this specific component.