The Weidmüller 2753450000 is a split-core current transformer designed for precise measurement of load current consumption using RMS value methods. It features a primary current rating of 1200 A and a maximum secondary current of 5 A. The device supports a load capacity of 5 VA with a tolerance class of 0.5. Designed for DIN rail mounting, it accommodates asymmetrical cable feed-through. Operating temperatures range from -5 °C to +40 °C, with physical dimensions of 58 mm in length and 198 mm in height.
Verify that the required primary current does not exceed 1200 A and the burden does not surpass 5 VA. Confirm compatibility with the specific cable cross-section for the split-core aperture. Ensure the operating environment remains within the specified temperature range of -5 °C to +40 °C. Check that the tolerance class of 0.5 meets the precision requirements of the application circuit.
Select this component when non-intrusive current measurement is required for high-current applications up to 1200 A. The split-core architecture facilitates retrofitting into existing electrical installations. Consider the 5 VA load limit when connecting downstream instrumentation or relay coils. Verify DIN rail mounting compatibility and spatial constraints given the 198 mm height dimension.
This part belongs to the KCMA series of industrial current transformers manufactured by Weidmüller. The series provides solutions for monitoring electrical loads in automation and energy systems. The model number 2753450000 corresponds to the specific configuration with 1200 A primary current and 5 A secondary output.
Cross-reference with other KCMA series models if different primary current ratings are needed. Ensure any substitute maintains the split-core form factor and 0.5 tolerance class for equivalent performance.