855-5101/800-000 is listed in the Current Sense Transformers range at ChipApex. The manufacturer field lists WAGO Corporation. Its product description is CURR SENSE XFMR 800A CHAS MNT. Review the specifications below when checking this part for your BOM.
The WAGO 855-5101/800-000 is a split-core current transformer designed for chassis mounting. It features a primary rated current of 800 A and a secondary rated current of 1 A. The device has a rated power of 0.5 VA and an accuracy class of 0.5. Operating within a frequency range of 50 Hz to 60 Hz, this component provides reliable current sensing capabilities for industrial applications requiring precise measurement integration.
Verify the specific part number suffix against official WAGO documentation to confirm exact specifications. Ensure compatibility with existing chassis mounting requirements and secondary circuit loads. Confirm that the 0.5 VA burden rating meets the connected instrument's requirements. Check for RoHS compliance status if required by project specifications. Validate the 800 A primary current rating matches the application's maximum load expectations.
Select this model when retrofitting is required without breaking primary conductors. Consider the 0.5 VA rated power to ensure the connected meter or relay does not exceed the transformer's capacity. Verify that the 800 A primary current aligns with the system's nominal operating range. The split-core architecture is essential for installations where cable removal is impractical or unsafe.
This component belongs to the WAGO 855 series of Rogowski coils and current transformers. The series emphasizes high resolution and space savings while maintaining Class 1 measurement accuracy per EN 61869 standards. These devices are engineered for modern production methods that eliminate saturation effects across wide primary current ranges.
Consult official WAGO cross-reference lists for direct substitutes. Verify that any replacement maintains the 800 A primary rating, 1 A secondary output, and 0.5 VA burden capacity. Ensure mechanical dimensions and mounting style match the existing chassis setup.